DEHEN
DEHN vap surge protector DVA CSP 3P 100FM
DEHN vap surge protector

FEATURES

  • Type 1 + Type 2 Combined Protection
  • High Discharge Capacity
  • RADAX Flow Technology
  • Tool-Free Module Replacement
  • Comprehensive Status Indication

APPLICATIONS

  • Mobile Radio/Cell Sites
  • 230/400V Power Supplies
  • Industrial & Commercial Facilities
  • Renewable Energy Infrastructure
  • End-to-End System Protection

The DEHNvap DVA CSP 3P 100FM is a prewired Type 1 + Type 2 combined lightning current and surge arrester. It is based on spark-gap technology and is specifically optimized for protecting power supply systems in mobile radio base stations. A standout feature is its RADAX Flow technology, which provides exceptionally high follow-current limitation and extinguishing capability, ensuring no tripping of 32 A gG fuses up to short-circuit currents of 25 kArms. The modular design uses a pluggable protection module for easy, tool-free replacement. It features an integrated visual status indicator (green/ok, red/faulty) and a remote signaling contact for constant status monitoring

MODEL ENCODING

DVA DEHNvap product series
-
CSP Cell Site Protection
-
3P 3 Poles
-
100 100 kA
Model
DVA CSP 3P 100 FM
General
Part Number
900 360
SPD Classification (EN/IEC)
Type 1 + Type 2 / Class I + Class II
Number of Poles
3P+N
Electrical
Max. Continuous Operating Voltage (Uc)
255 V (50/60 Hz) [L-N] / 264 V (50/60 Hz) [N-PE]
Lightning Impulse Current (Iimp)
25 / 100 kA (10/350 µs) [L-N]/[N-PE]
Lightning Impulse Current Total (Itotal)
100 kA (10/350 µs)
Nominal Discharge Current (In)
25 / 100 kA (8/20 µs)
Voltage Protection Level (Up)
≤ 1.5 kV (L-N / N-PE)
Follow Current Extinguishing Capability (Ifi)
25 kArms / 100 Arms
Response Time (tA)
≤ 100 ns
Mechanical
Dimensions (Width)
8 modules / 144 mm (DIN 43880)
Mounting Type
35 mm DIN rail (EN 60715)
Degree of Protection
IP 20
Housing Material
Red thermoplastic, UL 94 V-0
Connection Cross-section (Solid/Flexible)
Max. 50 mm² / 35 mm²
Environmental
Operating Temperature Range
-40 °C to +80 °C
Standards & Approvals
Compliance
EN 61643-11, IEC 61643-11
Approvals
KEMA, UL
Signaling
Remote Signaling Contact Type
Floating changeover contact
Switching Capacity (AC)
250 V / 0.5 A